Pump control @@&name@@
Control of a 1-stage motor, normally for a circulation pump, with anti-block protection function. The control has 3 levels:
Automatic requirements.
- Requirement for enabling, e.g. by clock or a system switch
- Requirement, in which the requirement can be parameterised through 2 causes, according to outside air temperature (smaller/greater limit value or inactive) and/or signal requirement (typically valve position).
Both automatic requirements have equal rights.
Anti-block protection
An anti-block protection can be set, it controls the duration of the drive's rundown time. The anti-block protection mechanism is centrally defined.
Operation data / Maintenance
A metering of the operating hours and the switching cycles take place. When it reaches the set maximum value, a warning signal is issued. This can be reset via a central acknowledgement or separately and only for this drive.
Parameter |
Value |
Building management system switch (1=Auto, 2=Off, 3=On) |
@adj_HMI.0p@ |
Switch-off delay |
@adj_Nachlauf.1p@ s |
Pre-selection for anti-block protection function (1=No, 2=Yes, 3=not available) |
@adj_AbsVorwahl.0p@ |
Requirement according to outdoor temperature (1=without, 2=smaller, 3=greater) |
@adj_AtFunktion.0p@ |
Limit value for outside air temperature |
@adj_AtGrenzwert.1p@ °C |
Requirement according to control signal (1=without, 2=(or) smaller, 3=(and) greater) |
@adj_YFunktion.0p@ |
Limit value of control signal |
@adj_YGrenzwert.1p@ % |
Number of starts until maintenance signal is issued |
@adj_SchaltungenMax.0p@ |
Number of operation hours until maintenance signal is issued |
@adj_StundenMax.0p@ Std. |