BACnet objects

 

Parts of the data points can be provided for BACnet. High value options also contain the low value ones.

 

Parameter

Value

Parameterised option

@adj_BACnet.0p@

     

Opt.

Data point

Object information

1

Free cooling: Pre-selection

MV

1

Free cooling: Minimal outside air temperature

AV

1

Free cooling: Hysteresis between actual value of ambient temperature and actual value of outside air temperature as switch-on criterion

AV

1

Free cooling: Hysteresis between actual value of ambient temperature and actual value of outside air temperature as switch-off criterion

AV

1

Free cooling: Hysteresis between actual value of ambient temperature and set point of ambient temperature as switch-on criterion

AV

2

Cooling protection: Pre-selection

MV

2

Cooling protection: Switch-on at actual value smaller than

AV

2

Cooling protection: Switch-off at actual value greater than

AV

3

Enforced cooling: Pre-selection

MV

3

Enforced cooling: Start hysteresis

AV

3

Enforced cooling: Switch-off hysteresis

AV