System switch 1-stage
@@&name@@
Enabling of switch for 1-stage systems. The
enabling of switch has 3 levels:
- Manual switch. This switch has the
positions Off – Auto – On. Highest priority. If there is no manual switch
available, this parameter can be used for instance for a higher level
virtual operation. If BACnet is activated, this parameter then shows
<Auto>, if the resulting system enabling of BACnet is identical with
the requirement (regardless of whether the system should be Off or On). If
a different operating mode is enforced through BACnet, the corresponding
status is displayed (e.g. On or Off)
- Building management system switch.
Effective only if the manual control switch is on <Auto>. This
switch has the positions Off - Auto – On. This parameter is normally used
in the virtual operation in a SCADA or WebPanel.
- Automatic requirements. Effective only if
the manual control switch and the building management switch are in auto
mode. There are two types of automatic requirements: Clock and special
function outside the normal operating times.
Parameter
|
Value
|
Building management system switch
(1=Auto, 2=Off, 3=On)
|
@adj_Vorwahl.0p@
|
Timing function (0=in control, 1=by
SCADA)
|
@adj_UhrTyp.0p@
|
Selected switching channel in control
(1..10 = switching channel 1..10, 11=not used)
|
@adj_Kanal.0p@
|