Re-heater controller @@&name@@

 

Re-heater controller, normally influencing the supply air temperature. This does NOT switch to active mode, but is activated by a preceding controller if need be (e.g. preheater). Minimum and maximum values are active only with attached controller enabling (also if the controller is inactive)

 

During dehumidification, the controller turns to active mode and adjust the temperature. If the dehumidification controller turns off the dehumidification (control signal dehumidify smaller than 5%), the re-heater deactivates as well and the cooler controller assumes the temperature control. See also Dehumidification controller.

 

Parameter

Value

Unit control variable

°C

Unit controller signal

%

Set point preselection (0=constant, 1=Set point function)

@adj_SollwertWahl.0p@

Set point control variable (if constant)

@adj_Sollwert.1p@

Proportional range

@adj_P_Band.1p@

Reset time

@adj_I_Zeit.1p@ s

Differential time

@adj_D_Anteil.1p@ s

Dead band

@adj_Totzone.1p@

Scanning time of the controller

@adj_Abtasten.1p@ s

Controller signal (0=Auto, 1=Manual)

@adj_YWahl.0p@

Controller signal with manual intervention

@adj_YHand.1p@

Minimum control variable

@adj_YMin.1p@

Minimum control variable

@adj_YMax.1p@