S-Bus communication problems with PCD3

FAQ #100336

Since the communiction on the PCD3 is not handled the same way as on PCD2, communication problems can occur with RCU (Midi-RIO) modules.

 

To solve this problem, the turnaround delay has to be increased. This can be done by writing the value 0xE00 in Reg0/Byte1. The turnaround delay will then be 1ms and the communication with the RCU-Modules will work properly.

 

Categories

Third Party Products

Last update: 15.05.2015 10:48

First release: 09.03.2005 13:02

Views: 2411

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download