The modem library xx7 indicates an error -104

FAQ #101324

What does the error -104 of the modem library mean?

 

Problem
The xx7 modem library indicates an error -104.

Reason
This error indicates that an error occured during the initialisation of the port. Usually because the selected mode is not valid / supported.
Per example on the PCD3.Mxx7 the port 0 is per default configured as MPI port, see the related FAQ for more details. In case the modem library is using port 0 as well, this leads to error -104.

Solution
The default MPI configuration can be transfered to an other port (see related FAQ). In case the modem should be used with MPI protocol this has to be handled with the modem libary.


 

Categories

xx7 Series / CPU and operating system

xx7 Series / Communication

Last update: 01.06.2015 01:22

First release: 30.10.2009 13:41

Views: 4278

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download