Why is it not possible to create / open Profibus DP files in PG5 2.0?

FAQ #101435

PG5 2.0 shows an error that the DevTable.dat is missing. DP files cannot be created or opened anymore

 

Problem
It is not possible to open .DP files. PG5 2.0 is showing an error DevTable.dat missing.

Solution
Check under C:\Documents and Settings\All Users\Saia-Burgess\PG5_20\S-Net Files\
if the DevTable.dat is available. Most probably the file was renamed to DevTable.old. Just change the name back to DevTable.dat and it should work again.

 

Categories

PG5 2.0

Last update: 26.05.2015 15:36

First release: 03.06.2010 12:18

Views: 1383

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download