• PCD1.G360x-C15

     

     

  • E-Line room control module

PCD1.G3600-C15:

E-Line input/output module for room automation
freely programmable
Supply 24 VAC/VDC
8 digital inputs 24 VAC/VDC
3 relay changeover 230 VAC / 30 VDC, 6 A, max. inrush current 15 A
1 relay changeover 230 VAC / 30 VDC, 10 A, max. inrush current 65 A
4 Triacs 24 VCA or 230 VAC/1 A
4 analog inputs 12 bits, 0...10 V, ±10 V,
 0(4)...20 mA, Pt/Ni 1000, NTC,
 0...2500 Ohm, 0...7500 Ohm, 0...300 kOhm
4 analog outputs 12 bit, 0...10 V (3 mA max.)
3 interfaces: RS-485 (S-Bus), USB & NFC (Service)

 

PCD1.G3601-C15: 

With auxiliary RS-485 interface

 

 

  • PCD1.G1100-C15

     

     

  • E-Line light & blind module

     

     

E-Line input/output module for light & blind
freely programmable
Supply 24 VAC/VDC
4 digital inputs 24 VAC/VDC
2 relay change over 230 VAC / 30 VDC, 8 A, max. inrush current 15 A, incl. galvanically isolated current measurement
2 analog outputs 12 bits, 0...10 V (3 mA max.)
3 interfaces: RS-485 (S-Bus), USB & NFC (Service)

Documentation

System Catalogue : E-Line

Extract PP26-215_A0160 System Catalogue : E-Line

ENG14 .pdf 5.83 MB Download
FRA14 .pdf 5.86 MB Download
GER14 .pdf 5.85 MB Download
ITA14 .pdf 5.84 MB Download

System Catalogue : Room Automation

Extract PP26-215_B0400 System Catalogue : Room Automation

Room automation is a crucial component for room comfort and also reduces operating costs to efficient levels. Energy efficiency therefore plays a vital role along with a comfortable interior temperature and the intuitive operation of the various room functions.

This can be achieved by room automation from SBC.

ENG14 .pdf 4.48 MB Download
FRA14 .pdf 3.85 MB Download
GER14 .pdf 3.85 MB Download
ITA14 .pdf 3.83 MB Download

E-Line-Room-Control

Flyer PP31-026 E-Line-Room-Control

DUT03 .pdf 0.96 MB Download
ENG03 .pdf 0.95 MB Download
FRA03 .pdf 0.95 MB Download
GER03 .pdf 0.99 MB Download
ITA03 .pdf 0.95 MB Download

PCD1.G360x-C15 E-Line room control module

Datasheet PP31-110 PCD1.G360x-C15 E-Line room control module

The fully programmable module with a housing width of 105 mm (6 HP) can be
controlled via RS-485.

ENG02 .pdf 1.35 MB Download
FRA02 .pdf 0.99 MB Download
GER02 .pdf 1.35 MB Download
ITA02 .pdf 0.98 MB Download

PCD1.G1100-C15 E-Line Licht & Beschattungsmodul

Datasheet PP31-111 PCD1.G1100-C15 E-Line Licht & Beschattungsmodul

The module has a housing width of 35 mm (2 HP) that is compatible with electrical control  cabinets, is controlled via RS-485 and enables light and blind control.

ENG03 .pdf 0.89 MB Download
FRA03 .pdf 0.87 MB Download
GER03 .pdf 0.87 MB Download
ITA03 .pdf 0.87 MB Download

E-Line Programmable Quick Start

Presentation E-Line Programmable Quick Start

E-Line Programmable Quick Start .pdf 0.91 MB Download

Minimal Firmware configuration

The minimum Firmware for the head station is 1.24.XX

 

 

Firmware used in production

Firmware used in production PCD1.E-Line programmable modules and RIO I/O modules

Firmware Package 1.04.24/1.04.25 Firmware used in production PCD1.E-Line programmable modules and RIO I/O modules

This firmware is used in the PCD production and the PCD1 E-Line programmable modules and RIO I/O modules are shipped with this firmware.

FW 1.04.24

- for the programmable I/O modules:
PCD1.G1100-C15
PCD1.G360x-C15
PCD1.F2611-C15
PCD1.W5300-C15

- for the RIO modules:

PCD1.B1000-A20
PCD1.B1020-A20
PCD1.G5000-A20
PCD1.G5010-A20
PCD1.G5020-A20

 

FW 1.04.25

- for the RIO modules:

PCD1.B1010-A20

 

 

1.04.24/1.04.25 .zip 0.71 MB Download

Good to know

PG5 2.1.410 or later is to be used for working with the PCD1 E-Line


Good to know

The differences between firmware version 1.04.07 and 1.04.24 are listed in FAQ 101990

PCD1 / E-Line

  • No Refresh from State of I/O's from E-Line Rio- Moduls after Fbox Update (FAQ #102001)
  • What is the meaning of E-Line RIO – Leds & status specifications (FAQ #101998)