Motor signals 2-stage @@&name@@

 

Logging of the prevalent motor failures, like operating feedback, rotary speed monitoring, motor protection, Rep.switch and manual control.

 

 

 

 

 

 

To prevent ghost signals in case of a fuse failure, a rejection of signal can take place depending on the associated voltage monitoring.

 

The collective error of the motor-related collective error always consists of the 3 standard signals - 'operating feedback absent', 'motor protection activated' and 'process feedback absent'.

. Alternatively, it can be also parameterised whether the signals Rep. switch and/or manual intervention should be likewise included in the collective error signal.

 

Parameter

Value

Operating feedback, delay

@adj_BetriebVerzoeger.1p@ s

Process feedback, normal status of the issuer (0=NO, 1=NC)

@adj_ProzessNoNc.0p@

Process feedback, delay

@adj_ProzessVerzoeger.1p@ s

Motor protection, requiring acknowledgement (0=No, 1=Yes)

@adj_MotorQuitTyp.0p@

Motor protection, normal status of the issuer (0=NO, 1=NC)

@adj_MotorNoNc.0p@

Motor protection, rejection of failure in case of absent fuse (0=never, 1=always, 2=230 VAC, 3=24 VAC, 4=24 VDC, 5=phase monitor, 6=control voltage)

@adj_MotorSpgGrp.0p@

Rep. switch, requiring acknowledgement (0=No, 1=Yes)

@adj_RepSchalterQuitTyp.0p@

Rep. switch, normal status of the issuer (0=NO, 1=NC)

@adj_RepSchalterNoNc.0p@

Rep. switch, rejection of failure in case of absent fuse (0=never, 1=always, 2=230 VAC, 3=24 VAC, 4=24 VDC, 5=phase monitor, 6=control voltage)

@adj_RepSchalterSpgGrp.0p@

Manual intervention, normal status of the issuer (0=NO, 1=NC)

@adj_HandeingriffNoNc.0p@

Manual intervention, rejection of failure in case of absent fuse (0=never, 1=always, 2=230 VAC, 3=24 VAC, 4=24 VDC, 5=phase monitor, 6=control voltage)

@adj_HandeingriffSpgGrp.0p@

Collective error additionally includes (1=none, 2=Rep. switch, 3=manual intervention, 4=both)

@adj_SsmTyp.0p@

Associated fuse monitoring

@@&ref@@