======================================================================================================================== 16.03.2018 Stephan Hintze Version SP2.7x.241 - BACnet - EventInhibit > wrong referenced Flag if set back to BACnet Device Object ======================================================================================================================== 05.01.2018 Stephan Hintze Version SP2.7x.240 - BACnet - Calendar : mapped value not touched when BACnet enabled but Stack not running or during start up. Out-Value set to zero ======================================================================================================================== 18.12.2017 Stephan Hintze Version $2.7x.237 - Analogue Values - Sensor : EventInhibit was always written by FBox, now only once written when back to normal and no RefEventInhibit active ======================================================================================================================== 07.12.2017 Stephan Hintze Version $2.7x.236 - BACnet - New FBox: Status-Flags - Controls - All FBoxes: If BACnet Standard 2014 (or newer), Status-Flags assigned to be accessed via new BACnet Status-Flags FBox - Controls - Continous: If BACnet enabled, Prio8 and Ovr was written also to Prio16 ======================================================================================================================== 20.11.2017 Stephan Hintze Version SP2.72.235 für PG5 2.2 Version SP2.73.235 für PG5 2.3 - Alarming - Mot 1/2/3 - order of alarms in ASV was wrong ======================================================================================================================== 20.11.2017 Stephan Hintze Version SP2.72.230 für PG5 2.2 Version SP2.73.230 für PG5 2.3 ======================================================================================================================== 15.11.2017 Stephan Hintze Version SP2.70.230 - BACnet > Trendlog > new generic FBox - BACnet > Structured View > new generic FBox - All BACnat AddOn files improved for new TR and SV FBox ======================================================================================================================== 13.11.2017 Stephan Hintze Version $2.70.222 - MaxIndex for R in Controller Macros Family > If IRM > 3999 ======================================================================================================================== 26.10.2017 Stephan Hintze Version $2.70.221 - BACnet > new FBox Structured View > need modification in all BACnet AddOn files (Rev. 14 done) - BACnet > Client > Binary Write > 2.70.010 > Priority enhanced to 17 = relinquish default - BACnet > Client > Multi-state Write > 2.70.010 > Priority enhanced to 17 = relinquish default - BACnet > Client > Analog Write > 2.70.010 > Priority enhanced to 17 = relinquish default, new parameter PCD Increment: FBox replaced ======================================================================================================================== 22.10.2017 Stephan Hintze Version $2.70.220 - Categories BACnet, Alarm, OnlineIO, Trend and Unit introduced - All Families done ======================================================================================================================== 20.10.2017 Stephan Hintze FBOX LIBRARY MOVED TO FBoxBuilder_23 FOLDER DUE TO ADJUST CATEGORIES (PG5 2.2/2.3 INSTALLER NEEDED) ======================================================================================================================== 18.10.2017 Stephan Hintze Version $2.70.211 - Systems > Boiler > Correction for $2.70.204 was wron implemented, forced compile error due to wron constant ======================================================================================================================== 11.09.2017 Stephan Hintze Version SP2.70.210 - Service pack - BAcnet Deive Rev. 14 > PcdInRef alwa incremented, error after 3 times delay when PcdInRef != PV, Autorecover ======================================================================================================================== 03.08.2017 Stephan Hintze Version $2.70.204 - System - All System 1/2/3, Hot Water, Boiler: with BACnet, from Auto no Off/... memorization was wrong, value has to be writtem 2 times ======================================================================================================================== 01.08.2017 Stephan Hintze Version $2.70.203 - BACnet - Event Inhibt : Hilfe DE war teilweilse NL ======================================================================================================================== 31.07.2017 Stephan Hintze - BACnet - Master AddOn von Y: übernommen. 27.07.2017 - René Zuch - Implemented a list DDC_NC_Reference.CSV that shows all BACnet Alarms and the corresponding NC ======================================================================================================================== 26.07.2017 Stephan Hintze Version SP 2.70.202 - BACnet - Scheduler A/B/M > Old FBoxes hidden, New FBoxes 2.7.5 with Next Time/Value Feature ======================================================================================================================== 24.07.2017 Stephan Hintze Version SP 2.70.201 - BACnet - Trenbdlog > Help completed ======================================================================================================================== 04.07.2017 Stephan Hintze Version SP 2.70.200 - ServicePack with latest fixes/improvements ======================================================================================================================== 30.06.2017 Stephan Hintze Version $2.70.191 - BACnet Rev. 14 > macro "_DDC27_shSmSpgPol" with "AlmSupAct" wrong behaviour (BACnet Rev. 14) ======================================================================================================================== 26.06.2017 Stephan Hintze Version $2.70.190 - Initialisation > System Alarm: STR for "Anlage" and "Gruppe" introduced, used by AlarmServer The "Anlage"-Nr is created automatically, starts by one and each System Alarm FBox increments value. FBox is disabled, old projects can be compiled, but Alarm Server supported. - Initialisation > New FBox System Alarm: Supports Alarm Server Parameter for "Alarm-Group" Renaming of parameter "Group" > "Priority" - Initialisation > Alarm Header > Introduced STR for Alarm Server CSV and ASV file name ======================================================================================================================== 19.05.2017 Stephan Hintze Version 2.70.151 SP - BACnet Device Rev. 9 > Test for FW was not working properly for older PG5 versions which do not know FW 1.28.xx + ======================================================================================================================== 04.05.2017 Stephan Hintze Version 2.70.150 SP - preperation for release - BACnet Client > Device Rev.14 > Language FR done - BACnet Client > Event Inhibit > Language FR done ======================================================================================================================== 24.04.2017 Stephan Hintze Version 2.70.150 SP - preperation for release - BACnet Client > Device > ID has become a Text, former Deximal > Update FBox will lead into build error. Text must be edited, after that build works. ======================================================================================================================== 04.01.2017 Stephan Hintze Version 2.70.143 SP - _DDC27_shSmSpgPol > Reset EventInhibit Flag only once ======================================================================================================================== 04.01.2017 Stephan Hintze Version 2.70.142 SP - Systems > Fan speed > 2.07.001 > Hysteresis On/Off former 0.0 to 100.0, now -10000.0 to 10000.0 - Controller > Family > Help all languages updated (was missing) ======================================================================================================================== 03.01.2017 Stephan Hintze Version 2.70.141 SP - BACnet Unit: If "None" was selected, unit was empty "", must be "no-units" - Control > OpenClose: If BACnet was selected without ManIntervention, MInt Object was still created. $IF wronf, tested for >2, must be >3 - NL : FBoxes with AlarmIndex > detailed info "Storingsmeldingen: n" completed - NL : FBoxes with HDLog > "Trend: xxx" completed - NL : BACnet > EventEnrollment > translation ======================================================================================================================== 09.12.2016 Stephan Hintze Version 2.70.140 SP - Alarming : Frost : If BACnet enabled and Polarity=1 (NC), BACstack was forcing wrong PV Air at startup > frostprogramm running Code for start-up moved from FBox end, now before executing frost-programm detection ======================================================================================================================== 05.12.2016 Stephan Hintze Version 2.70.139 SP - Control : Continous : If AlmIdx = 0 >> Alarmtexts have been still put in DDC_Alarming.csv - BACnet : Scheduler : If Prio8 is enabled, BACstack does not update PV of ref-object. Done by FBox after PowerOn/Download ======================================================================================================================== 23.11.2016 Stephan Hintze Version 2.70.138 Internal - BACnet > FBoxes Rev. 14 for nternal tests enabled ======================================================================================================================== 06.10.2016 Stephan Hintze Version 2.70.137 SP - Controls > Continous > If SWeb Ack was disabled in AlarmHdr, Error > wrong $IF/$ENDIF constellation ======================================================================================================================== 05.10.2016 Stephan Hintze Version $2.70.135 Internal ! - Controller > Master > BACnet AddOn File: New reference MVR_SP to use Y as setpoint for sequence - BAcnet > Loop > Checks if SetPoint has to be taken from SPR or MVR_SP ======================================================================================================================== 27.09.2016 Stephan Hintze Version $2.70.134 Internal ! - SetPoint > DEC.0 / DEC.1 / DEC.2 / Integer / Bin > Init PV after Download or BACnet failure not working fine when commandable and Prio8 enabled ======================================================================================================================== 26.09.2016 Stephan Hintze Version $2.70.133 Internal ! - Controls > Boiler > Copy FBox to migrate to 2.7 style with BACnet, Alarming and Trending ======================================================================================================================== 26.09.2016 Stephan Hintze Version 2.70.132 SP - BACnet > Client > Binary Object (O/V) Write - new FBox to write to server > Analog Object (O/V) Write - new FBox to write to server > MultiState Object (O/V) Write - new FBox to write to server ======================================================================================================================== 23.09.2016 Stephan Hintze Version 2.70.131 SP - BACnet > NC Recipient > IP address - internal integer value, if negative, not always correct converted into HEX ======================================================================================================================== 31.08.2016 Stephan Hintze Version 2.70.130 SP - SubMacro > _DDC27_SystemAlarmingGroupAck > if NoNc=open, GroupAck via SystemAlarm FBox was not working properly - All FBoxes with alarms that could be acknowledged > if SWeb Ack was disabled, group ack via SystemAlarm FBox was also suppressed - Init > AlarmHeader (2.70.001) > Parameter "Ack via SWeb" was not checked if Index = -1 - Controller > Cooler, PreHeater > first P-jump after direct activation not properly done (when using Start Sequence FBox) - Controller > PreHeater > first P-jump after direct heat-up eliminated ======================================================================================================================== 26.08.2016 Stephan Hintze Version 2.70.129 SP - Controller > Cooler, HeatRec, MixedAir, PreHeater, ReHeater > the controller flags are reset at coldstart > avoid wrong PID active after download ======================================================================================================================== 26.08.2016 Stephan Hintze Version 2.70.128 SP - BACnet > Calendar > language correction DE - BACnet > Recipient > language correction FR - Analog > Integer (MV) > language correction EN - BACnet > Trendlog > language correction EN ======================================================================================================================== 25.08.2016 Stephan Hintze Version 2.70.127 internal - BACnet > Event-Inhibit > symbol UseBACnet was not defined > - Analog > Sensor > AddOn ??? in TL event-inhibit-ref replaced with object name ======================================================================================================================== 23.08.2016 Stephan Hintze Version 2.70.126 SP - BACnet > Device Rev.14 > disabled (under development) - BACnet > Event-Inhibit > disabled (under development) ======================================================================================================================== 08.08.2016 Stephan Hintze Version 2.70.125 Beta - Alarming - Set point monitoring (2.07.001) > collective alarm (High or Low) was assigned to high alarm NC alarm group > wrong - High alarm now assigned to high alarm NC alarm group - Low alarm now assigned to low alarm NC alarm group ======================================================================================================================== 08.08.2016 Stephan Hintze Version 2.70.124 Beta - BACnet Rev. 14 preperation > "dry run" test of Event-Inihibit-ref and Event-Inhibit without BACstack > FBox code functionally OK. ======================================================================================================================== 02.08.2016 Stephan Hintze Version 2.70.123 - BACnet Rev. 14 preperation > macro "_DDC27_shSmSpgPol" with optional add. parameter "AlmSupAct" to be mapped in local Event-Inhibit > FBoxes introduce additional Flag for mapping > 1 Alarm, 1 Alarm/Message, 5 Alarms, Alarm delayed (not tested) ======================================================================================================================== 26.07.2016 Stephan Hintze Version 2.70.122 - Analogue > Sensor > Description input Rely all languages > Description parameter Reliability all languages - BACnet > Event-Inhibit > new FBox, inherits BACnet Device Event-Inhibit for "system" level - BACnet > Device > init FTI in runtime was not working ======================================================================================================================== 20.07.2016 Stephan Hintze Version 2.70.121 - Controller > All FBoxes > coldstart symbol not PUBL anymore ======================================================================================================================== 14.07.2016 Stephan Hintze Version 2.70.120 - Init > ABS (2.07.002) > BACnet > Enable was mapped wrong > inverted, new Prio01Enable flags > change in BACnet AddOn > impact on existing projects > Added Scheduler Y and 2p for Visi.Plus - Init > FD > change in BACnet AddOn > scaling counter fault/ok wrong ======================================================================================================================== 11.07.2016 Stephan Hintze Version 2.70.119 - System > Heating Circuit (2.07.001) > Macro [_BAC27_Trendlog_MaxBufferSize] moved from general into BACnet code segment - System > Hot Water (2.07.001) > Macro [_BAC27_Trendlog_MaxBufferSize] moved from general into BACnet code segment - System > Boiler (2.07.001) > Macro [_BAC27_Trendlog_MaxBufferSize] moved from general into BACnet code segment Remark: If no BACnet FBox is used, the macro is not included. Version 2.70.118 - Init > System Alarm (2.07.001) > predef. symbols "Grp4Msg" and "Grp5Alm" swapped, all languages - Init > Anti-block > help improved, all languages - BACnet AddOn files > removed some comments ======================================================================================================================== 13.06.2016 Stephan Hintze Version $2.70.117 - Preperation BACnet Rev 14 : inhibit / inhibit_ref (FBox disabled) ======================================================================================================================== 06.06.2016 Stephan Hintze Version 2.70.116 - Analog > Integer MI+MV: help text all languages - Controller > FB calculation PID > If no I was parametereized, the temp. value I/10 was not set ro zero > controller "humps around" a few 1/10 % ======================================================================================================================== 30.05.2016 Stephan Hintze Version 2.70.115 - BACnet > LimitEnable > Config High limit was wrong - BACnet > Device > Parameter ANSI >> ANSI/UTF-8 - Controls > OpenClose > Feedback emulation now also works if alarm messages suppressed ======================================================================================================================== 28.04.2016 Stephan Hintze Version 2.70.114 - BACnet >> AddOn files > DMS creation > TL Objectname was using Description ======================================================================================================================== 28.04.2016 Stephan Hintze Version 2.70.113 - BACnet >> ABS FBox now also generates SC objects for weekly action (+6 and +7) SC weekly setting = default value in SC ======================================================================================================================== 19.04.2016 Stephan Hintze Version 2.70.112 - Family Controls > FBox Open/Close >> Emulated feedback Open/Close now set 10 seconds before Operating period - some BACnet AddOn file using Description instead of ObjectName text ======================================================================================================================== 15.04.2016 Stephan Hintze Version 2.70.111 - Family Loop > FBox Split Y reactivated from DDC Suite 2.0 ======================================================================================================================== 13.04.2016 Stephan Hintze Version 2.70.110 Prepared for official release with PG5 2.2.110 - Text correction Control Motor 2 DE - Correction BACnet Scaling ABS AV object for hours ======================================================================================================================== 01.04.2016 Stephan Hintze Version 2.70.102 BACnet Device >> Check for PcdInRef=PV only after delay -> increment PcdInRef also only after delay ======================================================================================================================== 29.03.2016 Stephan Hintze Version 2.70.101 BACnet AddOn files >> update with latest Visi.Plus BACnet BMO definitions ======================================================================================================================== 17.02.2016 Stephan Hintze Version 2.70.100 official library ======================================================================================================================== 15.02.2016 Stephan Hintze Version 2.70.092 Service - All FBoxes with BACnet Trendlog : Macro "_BAC27_Trendlog_MaxBufferSize(Signal_TL , adj_O1TLBS)" moved to BACnet Sequence - Analog - Counter : Counted value was not copied from PcdInRef to stc_Zaehlwert ======================================================================================================================== 11.02.2016 Stephan Hintze Version 2.70.091 Service - FBox "System Alarm" not mandatory anymore. - Language IT reoved - Correction TL "Client-COV-increment" > not fix, now using COV of referenced object ======================================================================================================================== 10.02.2016 Stephan Hintze Version 2.70.090 Service - Last FR translations done ======================================================================================================================== 08.02.2016 Stephan Hintze Version 2.70.040 Service - Alarming: Implementation BACnet ACK via Acked-Transitions all FBoxes with (opt.) acknowledgement - Init / InitLib : new parameter to select if BACnet ACK is used or not ======================================================================================================================== 04.02.2016 Stephan Hintze Version 2.70.038 Service - Alarming: test and preperation for BACnet ACK via Acked-Transitions ======================================================================================================================== 03.02.2016 Stephan Hintze Version 2.70.037 Service - Family Init - New FBox InitLib Reduced - For "Light controller" no XOB, WD and FBox IO access ======================================================================================================================== 27.01.2016 Stephan Hintze Version 2.70.036 Service - Inactive/Active texts from FBox Properties reactivated, not using Devie OptionalText1/2 anymore ======================================================================================================================== 25.01.2016 Stephan Hintze Version 2.70.035 Service - NL Help corrupt due to text [NULL} in adjust comment line. correct = [NULL] Version 2.70.034 Service - FR translations ======================================================================================================================== 13.01.2016 Stephan Hintze Version 2.70.033 Service - FR translations ======================================================================================================================== 16.12.2015 Stephan Hintze Version 2.70.032 Service - Family Analog Values / Select >> if BACnet enabled, but BNT not linked or BACstack offm Value1 was not handled properly ======================================================================================================================== 09.12.2015 Stephan Hintze Version 2.70.031 Service - Family Controller / BACnet Loop Property Action >> mapping to display proper direction direct (cooling) / reverse (heating) ======================================================================================================================== 07.12.2015 Stephan Hintze Version 2.70.030 Service - Family Controls / FBox Open/Close >> Feedback was copied to Feedback, must be PcdInRef ======================================================================================================================== 13.11.2015 Stephan Hintze Version 2.70.028 Service - Preparation NL/FR translations ======================================================================================================================== 02.11.2015 Stephan Hintze Version 2.70.026 Service - Preparation FR, translations ======================================================================================================================== 23.10.2015 Stephan Hintze Version 2.70.025 Service - Preparation NL, translations ======================================================================================================================== 20.10.2015 Stephan Hintze Version 2.70.024 Service - Preparation NL, FBox groups ======================================================================================================================== 06.10.2015 Stephan Hintze Version 2.70.023 Service - BAcnet AddOn files with Visi.Plus DMS generation ======================================================================================================================== 30.09.2015 Stephan Hintze Version 2.70.022 Service - text corrections EN - System and Clocks : System Switches > if Prio8 only NULL-ed, Prio8 value is set back to Auto by FBox - FBoxes with SWeb alarms > if disabled (AlmIdx = 0), alarm was still mapped into System Alarm FBox. ======================================================================================================================== 28.09.2015 Stephan Hintze Version 2.70.021 Service - text corrections EN ======================================================================================================================== 22.09.2015 Stephan Hintze Version 2.70.020 Service - Version package for first release beta tester ======================================================================================================================== 16.09.2015 Stephan Hintze Version 2.70.014 Service - Alarming SWeb Ack > due to Polarity change for BACnet, adaption also for SWeb Ack necessary ======================================================================================================================== 14.09.2015 Stephan Hintze Version 2.70.013 Service - System > HeatingCircuit > no limitation min. SetPt 20°C, now calculated by curve, En/Disable via outdoor limit ======================================================================================================================== 11.09.2015 Stephan Hintze Version 2.70.012 Service - Alarming > 1 Alm/Msg and Delayed > wrong object name for profile-name > AddOn modified - Control > Drive BO > wrong PCS key in description > AddOn modified - BACnet Client Analog > wrong macro name > modified to _DDC27... ======================================================================================================================== 10.09.2015 Stephan Hintze Version 2.70.011 Service - BACnet > Calendar, Scheduler B/A/M > missing $ENDIF Version 2.70.010 Service - Version for parallel installation. Only FBoxes from 2.6 can be updatet to 2.7. FBoxes from 2.5 (like system clocks) must be replaced manually. ======================================================================================================================== 09.09.2015 Stephan Hintze Version 2.70.007 Service (Migrationsversion! Unterstützt "Replace" von 2.5er FBoxen) - Minor corections for DOC_DDC AddOn files ======================================================================================================================== 08.09.2015 Stephan Hintze Version 2.70.006 Service (Migrationsversion! Unterstützt "Replace" von 2.5er FBoxen) - AddOn files installed in lib folder. Search order 1. Device sub folder \AddOn\BACnet or \AddOn\Alarming 2. Project sub folder \AddOn\BACnet or \AddOn\Alarming 3. library folder ======================================================================================================================== 04.09.2015 Stephan Hintze Version 2.70.005 Service (Migrationsversion! Unterstützt "Replace" von 2.5er FBoxen) - BACnet Recipient FBox > Broadcast def. = No / Correction Macro Name DDC26 > DDC27 Version 2.70.004 Service - BACnet Device FBox > New = Communication control ======================================================================================================================== 31.08.2015 Stephan Hintze Version 2.70.003 Service (Migrationsversion! Unterstützt "Replace" von 2.5er FBoxen) - Some corrections if BACnet ON was "" > now working fine ======================================================================================================================== 28.08.2015 Stephan Hintze Version 2.70.002 Service (Migrationsversion! Unterstützt "Replace" von 2.5er FBoxen) - HeatRec : if dehumidifying now Y = Y-Min or Y-Max - Analog MI/MV : accepts only values from 1.. ======================================================================================================================== 24.08.2015 Stephan Hintze Version 2.70.001 Service (Migrationsversion! Unterstützt "Replace" von 2.5er FBoxen) - direct I/O access disabled if PCD Type = M6880 (Redundant, S.CPU.PcdType = 57) - BACnet alarmobjects splitted now BV if pre-manipulated - polarity for BI mapped and adapted in code ======================================================================================================================== 21.08.2015 Stephan Hintze Version 2.70.000 Service (Migrationsversion! Unterstützt "Replace" von 2.5er FBoxen) - DDC Suite 2.7 library modified for parallel Installation